CN
133-8250-9160
PFHFWSDj-k Fully Automatic Smoke & Fire Damper
Product / Cleanroom equipment

PFHFWSDj-k Fully Automatic Smoke & Fire Damper

Product Introduction
Main Technical Parameters:
Air leakage rate (at a differential pressure of 300 Pa): ≤ 700 m³/(m²·h)
Fusible link operating temperature: 280°C
Operating time: 3 seconds
Reset time: 20 seconds
Fire resistance rating of the valve: 1.5 h
Control voltage: DC 24 V
Resistance coefficient when the valve is fully open: < 0.5 

Structure:
Main components: valve body, valve blade shaft, shaft bushing, fusible link and actuator
All flanges are formed by integrated flange connection with a flange width of 30 mm

Thickness of rectangular valve body: L = 250 mm


Performance:
The valve remains normally open under standby conditions. In case of a fire, the smoke detector sends an electric signal (DC 24 V) via the control center. The electromagnet inside the actuator is energized for action, the valve closes automatically and outputs a closed electric feedback signal.
The valve can be manually closed, or automatically closed via fusible link action at 70°C.
It is equipped with a 6‑gear air volume adjustment switch.
Common smoke & fire dampers require manual reset, while fully automatic types adopt DC electric driving reset after actuation.

Message