PYHSDc-k Multi-louver Smoke Damper Outlet
Product / Cleanroom equipment

PYHSDc-k Multi-louver Smoke Damper Outlet

Product Introduction
Main Technical Parameters:
Air leakage rate (at a differential pressure of 300 Pa): ≤ 700 m³/(m²·h)
Micro-switch contact capacity: AC 380V, 0.5A
Control voltage: DC 24V
Resistance coefficient when fully open: < 0.5

Structure:
Main components: valve body, decorative air outlet, valve blade, shaft, shaft bushing and actuator

Overall thickness of the multi-louver smoke vent: L=250 mm (including the outlet face panel)


Performance:
It is installed in smoke extraction systems and kept normally closed at ordinary times. In case of a fire, the smoke detector sends an electric signal (DC 24V) via the control center. The electromagnet inside the actuator operates upon power excitation, and the valve opens automatically with an opening feedback signal output. The valve can also be manually opened and manually reset.